Mfg Part Number: AM12HKMG3-5-125VAC60-4
Alternate P/N: AM12HKMG35125VAC604
NSN : 5925-00-841-8670
NIIN : 008418670
CAGE Code : 74193
Manufacturer: Eaton Corp
Item Name : Circuit Breaker
Thank you for your interest in our available parts and components on NSN Target. Circuit Breaker is an item listed with the part number AM12HKMG3-5-125VAC60-4, and it is manufactured by Eaton Corp. This particular item AM12HKMG3-5-125VAC60-4 is currently available for purchase through our website today, and our team of industry experts are on standby 24/7x365 to provide rapid lead-times and competitive pricing. To begin the purchasing process, we invite you to fill out and submit an Instant RFQ form as provided through our website. Once received, a member of our staff will reach out to you in 15 minutes or less to provide a quote that has been personalized to fit your individual needs.
NSN Parts is a website that is owned and operated by ASAP Semiconductor, and we serve as a leading independent distributor of NSN parts and components that serve many industries and applications. Throughout our extensive part and manufacturer catalogues, we carry a variety of top requested components that you may need, including AM12HKMG3-5-125VAC60-4 with NSN 5925008418670 and other parts manufactured by Eaton Corp. Quality is of the utmost importance to us at NSN Parts, and we have established ourselves as an FAA AC 00-56B, AS9120B, and ISO 9001:2015 certified enterprise. Get started today with a personalized quote and experience how we are revolutionizing the parts procurement process.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-841-8670 Item Description: Circuit Breaker | 5925 | 008418670 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | U | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
Am12hkmg3-5-125vac60-4 | E | 9 | 3 |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | SINGLE POLE TYPE |
ADAQ | BODY LENGTH | 2.500 INCHES NOMINAL |
ADAT | BODY WIDTH | 0.750 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.938 INCHES NOMINAL |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AJEC | BOSS HEIGHT | 0.140 INCHES NOMINAL |
AKPX | POLE QUANTITY | 1 |
APNQ | ARC QUENCHING METHOD | AIR |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 5.0 AMPERES AC SINGLE LOCATION |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 125.0 AC SINGLE LOCATION |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC SINGLE LOCATION |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
CPRP | ULTIMATE TRIP TIME PER POLE IN SECONDS | 18.000 MINIMUM SINGLE LOCATION AND 70.000 MAXIMUM SINGLE LOCATION |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 10.000 MINIMUM AT 150 PCT SINGLE LOCATION AND 30.000 MAXIMUM AT 150 PCT SINGLE LOCATION AND 4.000 MINIMUM AT 200 PCT SINGLE LOCATION AND 10.000 MAXIMUM AT 200 PCT SINGLE LOCATION AND 1.400 MINIMUM AT 300 PCT SINGLE LOCATION AND 4.000 MAXIMU |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND MOISTURE RESISTANT AND EXPLOSION RESISTANT |
CRTK | SWITCH TERMINAL TYPE | TAB, SOLDER LUG |
FREQ | FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
THSD | THREAD SERIES DESIGNATOR | UNC |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.062 INCHES NOMINAL |
AEGJ | SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.611 INCHES NOMINAL |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 2000.0 AC SINGLE LOCATION |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRZ | AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
CQSM | SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE ONE |
CSSX | SWITCH CURRENT RATING AND TYPE IN AMPS | 5.0 AC AND 1.0 DC |
CSWP | SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 125.0 AC AND 50.0 DC |
TTQY | TERMINAL TYPE AND QUANTITY | 2 THREADED STUD |
“We Proudly Support Intrepid Fallen Heroes Fund that serves United States Military Personal experiencing the Invisible Wounds of War : Traumatic Brain Injury (TBI) and Post Traumatic Stress (PTS). Please visit website (www.fallenheroesfund.org) and help in their valiant effort”. |
We Hope that You Will Visit Us Again the Next Time You Need NSN Parts and Make Us Your Strategic Purchasing Partner.
Request for Quote